AN ORDINANCE AMENDING ORDINANCE #1555, dated
_MAY 1961, AND AS AMENDED, DECEMBER 1961
Section 610 (Reference Electrical Code - Chapter 6)
BE IT ORDAINED BY THE COMMON COUNCIL OF THE CITY OF
JEFFERSONVILLE, INDIANA:
1. FURNACE
Shall be on an individual circuit with no other outlet.
Conductor size shall be no less than #12 wire with ground.
Feed to a switch on furnace at a convenient location for main-
tenance. Fusing to be in main panel or at a disconnect near
main panel.
2. AUTOMATIC WASHER
Install a separate circuit with a grounded receptacle.
Conductor shall be no less than #12 wire and fused with no more
than a 20 ampere fuse.
3. AIR CONDITIONING
Install separate circuit, with grounded receptacle in the
case of remote units, and direct connection with disconnect for
central units. Conductor
on unit demand.
4. METAL TUBING
Shall be installed in all schools;
indus=tiaA!and institutional buildings.
of assembly - either public or provate,
size shall be #12 or greater, depending
chruches; commercial,
Lodges and other places
refer to N.F.P.A. #70 ASA -
C1 National Electrical Code, 1962 Edition, Article 520-4 Exception
#2.
(a) For all intent and purpose of the "City Building
Code" should read:
Where the area intended for public or private
assembly has a capacity of 100 persons - Remain-
der of exception #2 to remain the same. Capacity
shall be based on requirements stated in Section
401, Chapter 4, Part II, of "Buildings Rules
& Regular&ohs" of the "Administrative Building
Council of Indiana."
5. SPLICES: See Splices - Article 110-14 N.F.P.A. #70
ASA C1 National Electrical Code, 1962 Edition.
Conductorsshall be spliced or joined with approved splicing
devices, (See definition for pressure connector ), or by brazing,
welding or soldering with a fusible metal alloy. Soldered
splices shall first be so spliced or joined as to be mechanical
and electrically secure without solder and then soldered. All
splices and joints and the free ends of conductors shall be
covered with an insulation equivalent to that on the conductors.
(a) Definition for Pressure Connector:
A pressure wire connector is a device which establishes
the connection between two or more conductors,
or between one or more conductors and a terminal
by means of mechanical pressure and without the
use of solder.
(b) Exception: Screw type wire nut may be used for
fixture connections to conductor wire.